Environmental -20 to 60 degC 0 - 99 %RH
EMC Compliant 89/336/EEC, EN55022, EN50082-1,AS3548
Housing - extruded aluminium case 130 x 185 x 60mm with DIN rail mounting
Removable terminal blocks for ease of module replacement
Terminals suitable for 2.5sqmm conductors
LED indication for power supply, WDT, digital I/O, serial comms.
Digital Inputs
opto-isolated (5000V) inputs suitable for voltage free contacts or NPN transistor, contact wetting current 5mA
105-1 four inputs 105-2 four inputs 105-4 up to 16 inputs (4 inputs + 12 selectable I/O). The 12 selectable inputs are surge protected but not isolated.
Digital Outputs
105-1 four relay output contacts, normally open, AC3 2A 250V, 5A 120V / AC1 5A 250V / DC 30V 2A
105-2 one FET output 30VDC 500mA
105-3 eight FET output 30VDC 500mA
105-4 up to 16 FET output (4 outputs + 12 selectable I/O)
Analogue Inputs
"floating" differential inputs, common mode voltage 27V, 24VDC for powering external loops provided, digital filtering 1 sec.
105-1 two 4-20mA resolution 15 bit, accuracy 10 bit
105-2 six 0-20mA resolution 12 bit, accuracy 10 bit
Analogue Outputs
current sink to common, max loop voltage 27V, max loop resistance 1000 ohms
105-1 two 4-20 mA resolution 15 bit, accuracy 10 bit
105-3 eight 0-20 mA resolution 12 bit, accuracy 10 bit
Pulse Inputs
Specifications as per digital inputs
Max pulse rate 100Hz, pulse width min 5ms
105-1 one input (DI1)
105-2 105-4 four input(DI1-4) - first pulse input (DI1) max 1000Hz, pulse width min 0.5ms
Pulse Outputs
FET 30VDC 500mA max 100Hz
105-1 one
105-3 four (DO1-4)
105-4 four (DO1-4)
Battery supply 11.5-15.0 VDC
Normal supply 12-24 VAC or 15-30 VDC, overvoltage and reverse power protected
Mains supply 110-250 VAC available via plug-pack transformer
Battery charging circuit included for 1.2-12 AHr sealed battery
Solar regulator for direct connection of solar panel (up to 30W) and solar battery (100AHr)
Internal monitoring of mains fail status, solar charge status, and battery voltage. These values may be transmitted to remote modules for monitoring.
An internal inverter provides 24VDC 150mA for analogue loop supply.
Single channel, synthesised, direct frequency modulation
Synthesiser switching range 4MHz
Frequency / Channel spacing / Transmitter power
405 - 490 MHz / 12.5 KHz / 10 - 500mW
868 - 870 MHz / 25KHz / 10 - 500mW
Receiver sensitivity 0.4(V (-115dBm) 12dB SINAD
Signal detect / RSSI -120 to -100dBm
Conforms to Europe ETS 300 220 10 - 500mW EIRP
Expected line-of-sight range @ 10mW EIRP - 2km, @ 100mW EIRP - 5km, @ 500mW EIRP - 10 km
Range may be extended by using up to five intermediate 105U modules as repeater units
Aerial connector is BNC or SMA coaxial, and is protected by a gas discharge surge arrester
RS232/RS485 serial port 9600 baud, 8 bits, no parity, 1 stop bit
RS232 9pin DB9 female connector
RS485 max cable distance 2000 m terminal connections
Data transmission on "change-of-state" of inputs as well as integrity update transmissions.
The period for update transmissions is configurable. Data transmitted as bit stream data frame using a synchronous protocol with 16 bit CRC error checking. Automatic acknowledgment of error-free transmissions with up to 5 retries before communications fail is set.
Communications failure status may be configured as a digital output. Resetting of outputs on communications failure is configurable.
Transmission rates Radio 4800 bd Serial 9600 bd
Typical radio message transmission time 80ms
|
 |
 |
 |
|
|
|
|
|
|