9 - 30VDC / 12 - 24VAC
Battery charging circuit included for 12V back-up battery, max charge current regulated to 1A
Normal current drain
Modbus / DF1 version
12V 150mA; 24V 90mA
Profibus / Ethernet
12V 270mA; 24V 170mA
Add 5mA per active I/O
Current drain during radio transmission - add to above
12V 350mA; 24V 200mA
Modbus/DF1 version
-20 to 60 degC, 0 - 99 %RH
Profibus / Ethernet
0 to 60 degC, 0 - 95 %RH
EMC Compliant EN55022, EN50082-1, FCC Part 15
Housing - extruded aluminium case 130 x 185 x 60 mm, DIN rail mounting, removable terminal blocks for ease of module replacement, terminals suitable for 2.5sqmm wire
LED indication for processor OK, radio TX and RX, serial TX and RX, active status.
Modbus / DF1 4300 I/O points (analog plus discrete)
Profibus 416 I/O bytes
up to 1952 discrete inputs / 1952 discrete outputs
or up to 122 analog inputs / 122 analog outputs
Ethernet 2048 bytes input and 2048 bytes output
up to 4300 discrete I/O points
or up to 1024 analog inputs / 1024 analog outputs
Register size 16 bit
Number of remote 105U addresses 500
Single channel, synthesised, direct frequency modulation.
Frequency 869.525 MHz, 250KHz channel, 500mW
Approved to EN 300 220, AS4268.2, RFS29
Expected line-of-sight range, with unity gain antennas
500mW - 5km(869Mz) Range may be extended by up to four intermediate repeaters.
Radio communications can be configured for combination of event reporting (change-of-value), update time, read/write blocks and poll response.
Radio message includes system addressing, unit addressing, error-checking and configurable security encryption.
Communication control includes message acknowledgments and up to four re-transmissions.
Peer to peer addressing. Messages may be routed thru four intermediate repeater addresses.
Fail-to-transmit and fail-to-receive alarms configurable
Modbus RTU (binary) protocol, master / slave configurable.
RS232 or RS485, 300 - 19200 baud.
Allen-Bradley DF1 full-duplex specification. Acts as both Command Initiator and Command Recipient.
RS232 only, 300 - 19200 baud.
Profibus-DP Slave functionality according to EN 50170.
RS-485 optically isolated with on-board DC/DC converter, automatic baudrate detection (9600 bit/s - 12 Mbit/s)
10/100 Mbit/s, RJ45 transformer isolated interface
Modbus/TCP class 0, 1 and partially class 2 slave functionality
EtherNet/IP level 2 I/O Server CIP (ControlNet & DeviceNet)
Embedded Web system (Dynamic HTTP), on-board file system (1.4MB flash disc), user downloadable web pages through FTP server, Email functionality (SMTP)
Eight discrete I/O, individually configurable as input or output. Inputs suitable for voltage free contacts.
Outputs are FET, 30VDC 500mA.
Configuration via free Windows software
Diagnostics include on-line read/write of I/O registers, radio signal strength values from remote units, and off-line testing of data bus protocol.
|
 |
 |
 |
|
|
|
|
|
|
|