RM-505 Specifications
 
505U-2
General
  • Environmental -20 to 60degC 0 - 99% RH
  • EMC compliant 89/336 EEC, AS3548
  • Housing - IP65 painted aluminium enclosure 160 x 64 x 36 mm
  • Weatherproof connector for external connections.
  • BNC connector for aerial or coaxial cable connection.
  • LED indicators - Radio TX, Operation OK
    Power Supply
    505U-2-E

    • External supply 11.5-15.0 VDC overvoltage/reverse power protected.
    • Power consumption (12VDC) -
      • quiescent (sleep mode) 120µA
      • operating mode 10mA + analogue loop
      • during radio transmission (100 msec)
        • 170mA @ 250mW
        • 100mA @ 100mW
        • 50mA @ 10mW
    • Analogue loop supply internally generated 12VDC, 50mA
    • Power consumption increases for pulse inputs > 1Hz.
    505U-2-B

    • Suitable for use with BU-5 battery pack or any 3.5 - 5VDC battery pack.
    • Life of BU-5 is up to 1.4 years depending on input configuration
    • Internal monitoring of battery low voltage status - may be transmitted to remote modules as an "input".
    • Analogue loop supply internally generated 10VDC, 50mA
    • Power consumption increases for pulse inputs > 1Hz.
    Input Types
    I/O Power Supply Value
    Digital External Status
    Pulse External Count
    Analogue External Analogue
    Setpoint Internal Status
    Battery low Volts Internal Status


    Digital/Pulse Input

    Digital Inputs

    • two inputs, suitable for voltage free contacts / NPN or TTL 0-1.5 VDC on / 3.5-13VDC off
    • transmitted as digital status on change of input signal and on time elapsed since last transmission - update time period 1 min - 5.3 days, a separate update time may be configured for faster updates when the digital input is "on"
    Pulse Input

    • max rate 100 Hz (5 msec on time), transmitted as pulse count transmissions occur when count change exceeds configured amount, or on time elapsed since last transmission - update time 1 min - 5 days - change transmissions may be suspended if pulse rate exceeds a configured value to reduce radio traffic.
    • Up/Down Pulse Input - The two pulse inputs may be configured to a single count, to suit quadrature or incremental shaft encoder transducers.
    Analogue Input
    • 0 to 20 mA (4 - 20mA, 0 - 10mA) "floating" differential input
    • common mode voltage 15V
    • resolution 12 bit
    • accuracy < 0.1%
    • analogue measurement continuous or sampled - sample time configurable 1 min - 5 days
    • transducer warm-up time configurable 1 - 59 sec
    • analogue value transmitted on change of input signal or time elapsed since last transmission - change sensitivity configurable from 0.8 to 50%, update time configurable from 1 min - 5 days
    Setpoint Status
  • high and low setpoints generate internal digital status - setpoint status sets (on) when analogue value < low setpoint and resets (off) when analogue value > high setpoint status transmitted as per digital input
    Serial Port
  • RS232 DB9 female DCE, used for configuration and diagnostics
    Radio Transmitter
  • Synthesised transmitter
  • Frequency range 405 - 490 MHz.
  • Channel spacing 12.5KHz
  • Frequency configurable range 10MHz
  • Transmitter power (factory set) -
    • 500mW with 3dB aerial
    • 100mW / 10mW 0dB aerial
  • Conforms to EN 300 220, MPT1329, AS4268.2, NZ RFS29
  • Line of sight range -
    • 10km (6 mls) @ 500mW
    • 5km @ 100mW
    • 2km @ 10mW
  • Each transmission may be configured to be sent 1 to 5 times.
    Product Types
  • External 12VDC supply only - 505U-2-E
  • Battery Pack supply (3.5 - 5VDC) - 505U-2-B



  •  

    A Beijer Electronics Group Company